Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/07/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* RECALL FINAL WHEN ENERGIZED BY TEP & ALL WORK IS COMPLETED |
|
| 11/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RETAIN LICENSED ELECTRICIAN TO CORRECT THE ABOVE DEFFICIENCIES |
|
| 10/31/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDING ELECTRODE CONDUCTOR NEEDS TO BE CONTINOUS (NO CONNECTORS ALLOWED) EXOTHERMIC WELD OR REPLACE 2) NEED TO INSTALL (2) GROUND RODS 3) NEED TO SECURE GROUNDING CONDUCTOR TO PANEL (CLAMP) 4) PLUG IN USED OPENINGS AT MAIN 5) PANEL NEEDS TOBE SAFE TO RELEASE 6) PROVIDE ADDRESS ON PANEL |