Permit: T08EL02035

Parcel: 11104204B


Addresses:

3265 N KELVIN BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/09/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/07/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
RECALL FINAL WHEN ENERGIZED BY TEP & ALL WORK IS COMPLETED
11/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RETAIN LICENSED ELECTRICIAN TO CORRECT THE ABOVE DEFFICIENCIES
10/31/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUNDING ELECTRODE CONDUCTOR NEEDS TO BE CONTINOUS (NO CONNECTORS ALLOWED) EXOTHERMIC WELD OR REPLACE
2) NEED TO INSTALL (2) GROUND RODS
3) NEED TO SECURE GROUNDING CONDUCTOR TO PANEL (CLAMP)
4) PLUG IN USED OPENINGS AT MAIN
5) PANEL NEEDS TOBE SAFE TO RELEASE
6) PROVIDE ADDRESS ON PANEL