Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROTECT ALL ELECTRICAL WIRE LESS THAN 8'0" FROM GROUND ON FLOOR LEVEL 2. PROVIDE 2 - 8'0" GROUND RODS 6' APART 3. SHALL NOT MIX #14 & #12 WIRES 4. 15 AMP. MAX. BREAKER ON #14 WIRE 5. PROTECTIVE BUSHING REQ'D @ J-BOX |