Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND RODS DRIVEN AT TO MUCH OF AN ANGLE - 250.50 NEC 2. BOND BLD. STEEL, WATER PER 250.104 NEC 3. IDENTIFY HI LEG IF 120/240 DELTA 3/0 4. RISER CONDUIT SUPPORTS TO BE SEATED FLAT AGAINST BLD. STRUCTURE |