Permit: T08EL01944

Parcel: 118033050

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL01944

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
12/17/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) SEAL UNUSED KNOCKOUTS IN DEAD FRONT
12/03/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE LISTED DEADFRONT
2) GROUND ROD SYSTEM 6' APART
3) OMIT SHARP POINT SCREWS PANEL
4) SMOKE ALARM BEDROOM AND HALLWAY
04/10/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) WILL NEED TO HAVE A QUALIFIED ELECTRICIAN TO REPAIR ALL PROBLEMS
2) FOR RECONNECTION OF POWER, YOU WILL NEED TO:
A. CLEAN UP ALL WIRING INCLUDING SERVICE PANEL
B. REQUIRES APPROVED GROUNDING AT SERVICE
C. AT SUB-PANEL UNGROUNDED SYSTEM, POWER CHORD 2 WIRE WITH GROUND
D. POWER CHORD WRONG PLUG CAP. HOLES IN SERVICE PANEL
E. MISSING WALL OR CEILING COVERING
F. ALL 3 HOLE RECEPTACLES TO BE GFCI PROTECTED
G. MISSING DEAD FRONT AT SERVICE
H. ALL LIGHT FIXTURES TO BE WIRED PROPERLY
I. A/C UNITS TO BE ON THEIR OWN CIRCUITS
J. ALL ROMEX TO HAVE ROMEX CONNECTORS
3) PROBABLY MORE ITEMS TO LIST. CANNOT LIST ALL ITEMS AT ONE STOP. QUALIFIED ELECTRICIAN IS THE RIGHT DIRECTION TO GO.
04/09/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
GATES LOCKED
PROVIDE ACCESS TO UNIT
DOG IN YARD