Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/21/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/09/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BREAKERS 20 AMP PROTECTING 14 GAUGE WIRE 2) LARGE HOLE K/O IN SERVICE PANEL, NEEDS PLUG 3) ROMEX RUN TO ADDITIONS EXPOSED ROMEX, REMOVE OR WIRE CORRECTLY 4) SHED ADDITION NORTH SIDE EXPOSED ROMEX, CIRCUITS CUT WIRE NUTS, CIRCUITS TERMINATED, NO BOX 5) MISSING A CEILING FIXTURE KIT EXPOSED ROMEX SAME PLACE 6) LARGE ADDITION WEST OF KIT AND NORTH OF KIT. WILL CHECK FOR PERMITTED CONSTRUCTION, ONE IS A BEDROOM, ONE A FAMILY ROOM TYPE, HAS A HOLE IN CEILING WITH EXPOSED CU. WIRE, NO INSULATION ? 7) NEED WORKING SMOKE DETECTORS IN EACH BEDROOM, ONE IN HALLWAY 8) OLD PART OF HOUSE IS UNDERGROUNDED SYSTEM, CANNOT USE GROUNDED TYPE RECEPTS 9) PROBLEM WITH ROOF UNIT HEAT/COOLING ELECTRIC FEED, MOUNTING OF THE UNIT, DUCT WORK; ALL FLEX TYPE INTERIOR, EXPOSED. GAS LINE NOT SUPPORTED 10) NEED TO CLEAN UP UN-PERMITTED CONSTRUCTION. YOU WILL NEED AT MINIMUM A LICENSED ELECTRICIAN TO TAKE CARE OF PROBLEMS 11) I WILL TURN QUEST. OF PERMITTED CONSTRUCTION OVER TO THE DEPT. OF NEIGHBORHOOD RESOURCES FOR THE CITY OF TUCSON |