Permit: T08EL01909

Parcel: 134101090


Addresses:

8102 E MALVERN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/02/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/14/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) IDENTIFY ALL BREAKERS
2) YOU NEED A NEUTRAL FROM THE NEW PANEL TO THE BRADED SEU CABLE FEEDING THE SUB PANEL IN THE HOUSE
3) PANEL CALLS FOR USE OF SIEMENS BREAKERS. YOU USED CUTLER HAMMER
10/22/2008 ELECTRIC - FINAL Denied 1) UNGROUNDED SYSTEM INSIDE HOUSE, OLD SUB PANEL NOT CONNECTED TO NEW SERVICE. THIS IS JUST FOR THE UPGRADE FOR THE 200 AMP PANEL, RECALL FOR SUB PANEL WIRING
2) DON'T USE G.E. TYPE BREAKERS IN NEW PANEL (SEE LABEL)