| 10/14/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) MOVE SMOKE DETECTORS AT LEAST 3' FROM A/C REGISTERS 2) RECALL FOR FINAL AFTER POWER IS RESTORED, TO CHECK FUNCTION OF GFI'S AND SMOKEY LOCATIONS |
|
| 10/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ACCESS 2) CALLED NUMBER LEFT ON MESSAGE AT 10:25 AM AND NO ANSWER OR NO VOICEMAIL 2) NEED GFI RECEPTS AT KITCHEN COUNTER 3) SMOKIES ARE REQUIRED IN ALL BEDROOMS 4) DRYER VENT EXHAUST WILL REQUIRE A COVER WITH A FLAPPER DOOR 5) TPR LINE ON H20 HEATER MUST TERMINATE TO THE OUTSIDE AND BE INDEPENDENT 6) ELECTRICAL DIMMER KNOB MUST HAVE COVER PLATE 7) WAS ADDITION PERMITTED ? 8) NEED 2 GROUND RODS 6' APART WITH CONTINOUS GROUND WIRE 9) NEED TO BOND GAS AND WATER 10) ELECTRIC WIRES COVERED WITH STUCCO, MUST BE CONDUIT OR EXT. WIRE TYPE FOR MASONRY INSTALLATION |