Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERIFY PROOF PERMITTED KITCHEN IN GUEST HOUSE 2) GFCI PROTECT KITCHEN OUTLETS 3) EXPOSED WIRING KITCHEN OUTLETS 4) DEAD FRONT MISSING MAIN PANEL 5) SECURE RISER 6) SEAL KNOCKOUT 7) PROTECT ROMEX TO WATER HEATER 8) EXTEND PRESSURE RELIEF LINE 6"-24" FROM GROUND 9) PROVIDE PROOF ATTACHED STORAGE ROOM WEST SIDE WITH ELECTRICAL PERMITS AND INSPECTIONS 10) PROVIDE RIGID RISER TO SUB PANEL CONNECTION 11) GFCI PROTECT EXTERIOR LAUNDRY OUTLET 12) PROTECT ALL ROMEX UNDER 7' IN STORAGE FROM PHYSICAL DAMAGE. ALSO NAIL PROTECT THROUGHOUT 13) LABEL CIRCUITS SUB PANEL 14) MISSING COVER PLATES THROUGHOUT/SMOKE DETECTOR BEDROOM 15) HAZARDOUS ELECTRICAL STOVE 220 |