Permit: T08EL01892

Parcel: 129131570


Addresses:

747 E 33RD ST #02

Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
10/02/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VERIFY PROOF PERMITTED KITCHEN IN GUEST HOUSE
2) GFCI PROTECT KITCHEN OUTLETS
3) EXPOSED WIRING KITCHEN OUTLETS
4) DEAD FRONT MISSING MAIN PANEL
5) SECURE RISER
6) SEAL KNOCKOUT
7) PROTECT ROMEX TO WATER HEATER
8) EXTEND PRESSURE RELIEF LINE 6"-24" FROM GROUND
9) PROVIDE PROOF ATTACHED STORAGE ROOM WEST SIDE WITH ELECTRICAL PERMITS AND INSPECTIONS
10) PROVIDE RIGID RISER TO SUB PANEL CONNECTION
11) GFCI PROTECT EXTERIOR LAUNDRY OUTLET
12) PROTECT ALL ROMEX UNDER 7' IN STORAGE FROM PHYSICAL DAMAGE. ALSO NAIL PROTECT THROUGHOUT
13) LABEL CIRCUITS SUB PANEL
14) MISSING COVER PLATES THROUGHOUT/SMOKE DETECTOR BEDROOM
15) HAZARDOUS ELECTRICAL STOVE 220