Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/28/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/06/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) 20 AMP BREAKER IN PANEL TO BE A MURRAY TIME, 15 AMP NOT 20 AMP PROTECTING A #14 WIRE 2) MISSING LIGHT FIXTURES THRU-OUT 3) SMOKE DETECTORS REQUIRED IN EACH BEDROOM ONE AT HALLWAY 4) FROM LAST INSPECTION LABEL CIRCUITS 5) 90 AMP=60 DEGREE=1/0/75 DEGREE=#2 OK |
|
| 10/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE WATER BOND 2) LABEL CIRCUITS MAIN SERVICE PANEL DEAD FRONT 3) PROVIDE PROOF ELECTRICAL TO STORAGE PERMIT OR OMIT ELECTRICAL OR PROVIDE PERMIT 4) EXPOSED WIRING HALLWAY FIXTURE OR PLATE AND BATH FIXTURES 5) INSTALL WORKING SMOKE DETECTORS ALL BEDROOMS AND HALLWAYS 6) PROTECT HOMERUNS STORAGE ROOM FROM PHYSICAL DAMAGE UNDER 7' |
|
| 10/02/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PHONE-"NOT A WORKING NUMBER" 2) BOX CODE DOES NOT WORK 3) PLEASE RECALL |