Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2008 | ELECTRIC - FINAL | Approved | ||
| 10/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLAN CALLS FOR NEW PANEL AND BREAKERS TO BE RATED FOR 22KAIC 2. SECURE STRUT ON ROOF TO ROOF SURFACE 3. NEED PROPER WORKING CLEARANCE IN FRONT OF NEW PANEL 4. CONNECT EQUIPMENT GROUND TO PANEL ENCLOSURE |