Permit: T08EL01882

Parcel: 12706010A


Addresses:

40 N SWAN RD 03


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL01882

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/14/2008 ELECTRIC - FINAL Approved
10/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLAN CALLS FOR NEW PANEL AND BREAKERS TO BE RATED FOR 22KAIC
2. SECURE STRUT ON ROOF TO ROOF SURFACE
3. NEED PROPER WORKING CLEARANCE IN FRONT OF NEW PANEL
4. CONNECT EQUIPMENT GROUND TO PANEL ENCLOSURE