Permit: T08EL01879

Parcel: 116151730


Addresses:

482 N SILVERBELL RD

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/13/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) ITEM #2 STILL OPEN GROUND
10/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GFI RECEPTACLE IN KITCHEN NOT ON GFI CIRCUIT
2) BATHROOM GFI SHOWING OPEN GROUND ON TESTER
3) ALL RECEPTACLES THAT ARE NOT WIRED FOR GROUND NEED TO BE CLAMPED TO TWO HOLE PLUGS
10/03/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) PLEASE CALL IN FOR FINAL AFTER POWER IS ON
09/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED GFI PROTECTED RECEPTACLE AT KITCHEN COUNTER SPACE
2) SMOKIES IN BEDROOM NOT WORKING