Permit: T08EL01872

Parcel: 115060660


Addresses:

20 E FLORES ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/12/2009 ELECTRIC - FINAL Approved CLEARANCE OVER OUT BUILDING OK PER NESC AND TEP AGREEMENT.
06/11/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/08/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NO COMPLIANCE WITH PREVIOUS INSPECTION WRITE UP
2. A REINSPECTION WILL BE ASSESSED NEXT INSP. IF NO COMPLIANCE
3. CALLED MARCUS PRIOR TO INSP. AS REQUESTED
06/05/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. VERIFY NOTE, LAST INSP. FOR LIGHT FIXTURES, SERVICE DROP CONDUCTORS ABOVE ROOF
05/29/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
LIGHT FIXTURES TO COMPLY WITH 511.7 (NEC)
SERVICE DROP PER 230.24 ABOVE ROOF (NEC)
09/29/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXPOSED CONDUCTORS TO SIGN ON WALL
2. GROUNDED RECEPTACLES TO BE GFCI PROTECTED IN
AUTO SHOP
3. EXPOSED NM CABLES
4. CUT UP CORDS USED FOR LIGHT FIXTURES
5. OFFICE LIGHT HAS SPLICED CORD
6. OPEN EXPOSED CONDUCTORS IN BACK
7. PROPERLY INSTALL CONDUIT
8. LIGHTING IN BACK CORD HARDWIRED - USE APPROVED METHODS
9. SERVICE CONDUCTORS TOO LOW
10. WIRING AT SERVICE NOT TO CODE - NUMEROUS VIOLATIONS
11. PLEASE CONTACT A QUALIFIED ELECTRICIAN TO
REPAIR WORK