Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PENDING CARPORT |
|
| 09/24/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONFIRM THAT CARPORT EXTENDED TO WEST SIDE WAS PERMITTED AND INSPECTED 2) 2 GROUND RODS REQUIRED AT SERVICE PANEL 6' APART 3) BOND GAS LINE 4) OUTLETS AT KITCHEN COUNTER AND BATHROOM SHALL BE GFI PROTECTED 5) SMOKE ALARMS REQUIRED IN EACH BEDROOM AND HALL 6) GAS FLEX SHALL NOT PENETRATE FURNACE COMPARTMENT CAVITY |