Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL01836
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/11/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/06/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO EXPOSED WIRE BELOW 8' 2) KITCHEN COUNTER RECEPTACLES NEED TO BE GFI AND BATHROOM 3) JUNCTION BOXES AT ALL WIRE TERMINATIONS 4) SMOKE DETECTORS ALL BEDROOMS AND HALLWAYS 5) CHANGE BREAKS ON #14 WIRE TO 15 AMPS 6) DBL LUGGED BREAKER INSIDE |
|
10/03/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) LEFT MESSAGE AT 8:10 AM 2) NO ACCESS 9 AM 3) NO PRIOR INSPECTION RESULTS |
|
09/22/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO MESSAGE LEFT WITH REQUEST FOR INSPECTION 2) DOORS LOCKED 3) MISSING LIGHT FIXTURE REAR WALL EXTERIOR 4) 20 AMP BREAKERS PROTECTING #14 WIRE AT SERVICE PANEL 5) NOTE: I DON'T BELIEVE THIS HOUSE ROOF WAS DESIGNED TO CARRY A TILE ROOF COULD BE A SAFETY ISSUE |