Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1. UNIT LOCKED NO ACCESS UNIT TO BE OPEN FOR INSPECTION 2. GROUNDING ELECTRODE CONDUCTOR CUT & STOLEN FROM ALL 3 SERVICES ON BUILDING NEEDS TO BE REPAIRED OR REPLACED NEED COMPLETE GROUNDING ELECTRODE SYSTEM INCLUDING BONDING OF WATER & GAS GROUNDING ELECTRODE CONDUCTOR TO BE INSTALLED IN RACEWAY (PVC) TO PREVENT IT FROM BEING STOLEN. |