Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2008 | ELECTRIC - FINAL | Approved | APPROVED PER R. HOLLANDER OVER PHONE CONVERSATION ON 12/23/08 AT 11:29 AM PER L. HANLY'S APPROVAL OF C OF O | |
| 11/19/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ELECTRICAL ITEM RESOLVED - PLEASE CONTACT LEE RAY HANLY (SR. BLDG. INSP.) TO VERIFY INTEGRITY OF BUILDING STRUCTURES |
|
| 11/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
| 10/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* * PLEASE HAVE QUALIFIED ELECTRICIAN DO WORK 1. POST ADDRESS ON BUILDING 2. USE APPROVED BOX COVERS 3. PLEASE VERIFY PERMITS FOR NEW WALLS OR REMOVE 4. SUPPORT CONDUIT ACROSS CEILING 5. CABLE SHEATHING TO ENTER BOX 1/4" 6. GROUNDED RECEPTACLES ON UNGROUNDED WIRING 7. BOX OVERFILLED 8. DEVICES GROUNDED TO NEUTRAL CONDUCTOR 9. PLEASE VERIFY PLUMBING PERMIT OR REMOVE 10. USE APPROVED BOX WITH M/C CABLE 11. FILL UNUSED OPENINGS IN BOXES & PANEL 12. A DISCONNECTING MEANS IS NEEDED FOR WATER HEATER 13. PLEASE VERIFY PERMITS FOR NEW NM WIRING AND SUB-PANEL 14. EXPOSED NM WIRING 15. OUTDOOR BOXES & DEVICES TO BE FOR WET LOCATION 16. ROOF BOX FITTING BROKEN 17. MISSING HEATING/COOLING UNIT |