Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T08EL01753
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/16/2008 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
09/11/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED 2. INSTALL MISSING WALL PLATES 3. HAVE OPEN JUNCTION BOX IN CLOSET. INSTALL BLANK PLATE OR LIGHT FIXTURE (IN CLOSETS TO BE 100% ENCLOSED) 4. LIGHT FIXTURES IN CLOTHES CLOSET TO BE 100% ENCLOSED 5. INSTALL SMOKE DETECTORS IN BEDROOMS PER INSTRUCTIONS 6. REPLACE EXISTING SMOKE DETECTORS SO THEY ARE AC POWERED WITH BATTERY BACK UP 7. RECALL WHEN READY |