Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/09/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) METER FACE NEEDS TO BE SECURED-SO WHEN YOU OPEN-ONLY BOTTOM 1/2 OPENS, NOT WHERE IT ALL COMES OFF-SAFETY HAZARD 2) NEED TO WRAP WHITE TAPE ON NEUTRAL FEEDER COMING INTO METER 3) NEED TO PUT KNOCKOUT PLUG AT BOTTOM SERVICE PANEL AND MAKE A SMALLER HOLE FOR GROUND ROD 4) AT SUB PANEL NEED PROPER FLEX OR RIDGID ADAPTER INTO HOLE FOR OUTSIDE RECEPTACLE 5) RECEPTACLE NEEDS TO BE GFI PROTECTED WITH A BUBBLE COVER 6) NEED PROPER ATTACHMENT OF CLAMPS TO POLE NAILS ARE NOT APRROVED METHOD (WILL RUST) 7) MISSING FENCE COVER BOTTOM 1/2 OF SERVICE PANEL |