Permit: T08EL01720

Parcel: 11901076A


Addresses:

3354 S 6TH AV #A


Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL01720

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
06/04/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) STILL NEED REVISED PLANS
2) RECALL WHEN PANEL TIED IN
3) NEED PANEL DIRECTORY
05/20/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROPERLY INSTALL GROUND RODS 6' APART
2. INSTALL BOND DEVICES AT SERVICE NIPPLES AND RACEWAYS 250.92
3. SECURE GROUNDING ELECTRODE CONDUCTOR
4. INSTALL REJECTION PINS
5. IDENTIFY GROUNDING CONDUCTORS 250.119
6. SEAL ENTRANCES ABOVE CURRENT CARRYING PARTS
7. INSTALL ALL STRANDS OF CONDUCTORS UNDER TERMINAL LUGS
8. PLANS CALL FOR 3/4" GROUND RODS
9. REVISE PLANS TO WORK INSTALLED OR INSTALL AS PER PLANS
04/30/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*