Permit: T08EL01684

Parcel: 12007764B

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
09/08/2008 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
09/04/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VENT CAP WATER HEATER FLUE
2) EXTEND TPR VALVE 6" FROM GROUND
3) PROVIDE PROOF PERMIT LAUNDRY ADDITION WEST END AND ELECTRICAL IN STORAGE MAIN HOUSE
4) LABEL CIRCUITS EXTERIOR SUB PANEL
5) SEAL KNOCKOUT SUB PANEL
6) PROVIDE WEATHERED FITTINGS EXTERIOR BOXES
7) AT LEAST ONE BEDROOM MUST OPERATE PROPERLY FOR EMERGENCY EGRESS
8) MISSING SMOKE HALLWAY
9) POST UNIT NUMBER
10) REPLACE 14 GAUGE GROUND TO SUB PANEL WITH MINIMUM #6 GAUGE
11) CLEAN UP WIRING AT MAIN SERVICE MAIN HOUSE
09/03/2008 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
1. INSTALL SMOKE DETECTORS IN SLEEPING AREAS
2. INSTALL GFI PROTECTED OUTLETS IN BATHROOM AND AT KITCHEN SINK