Permit: T08EL01675

Parcel: 11206303A


Addresses:

2127 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/29/2008 ELECTRIC - FINAL Approved
09/26/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH #8 PREVIOUS INSPECTION
09/22/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ALL SERVICES IN AREA UNDERGROUND
2. USE LISTED MAST BRACE KIT
3. IDENTIFY NEUTRAL CONDUCTORS CLOSER TO WEATHERHEAD
4. PANEL CIRCUIT DIRECTORY TO BE AS PER 408.4 NO GENERAL LABELING AND NO ABBREVIATIONS
5. INSTALL SERVICE CONDUCTORS AS PER MANUFACTURES INSTRUCTIONS
6. MAINTAIN WIRE BENDING RADIUS
7. GROUNDING EQUIPMENT CONDUCTORS TO BE GREEN ENTIRE LENGTH
8. CORRECLTY IDENTIFY UNGROUNDED CONDUCTORS
9. SECURE CABLE TO JUNCTION BOX WITH APPROVED CONNECTORS
10. USE APPROVED & LISTED JUNCTION BOX - NOT OLD PANEL
11. CORRECTLY MAKE UP JUNCTION BOX