Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL01671
Inspection Description - ELECTRIC - FINAL
Inspection Status - Not ready for Inspection
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/06/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/06/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/15/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING CANNOT USE SMASHED EMT WITH MINERALLAC STRAP 2. BRANCH CIRCUITS (LOAD CONDUCTORS) CANNOT EXIT THROUGH TOP END WALL. SEE INSTRUCTIONS AND WARNING ON LABEL 3. PLEASE VERIFY 50 AMP. CIRCUIT FOR DRYER SHOULD IT NOT BE 30 AMP? 4. CANNOT USE TEK SCREW (SHEET METAL SCREW) FOR CONNECTION OF GROUND BAR TO JUNCTION BOX 5. PLEASE PROVIDE ROOF ACCESS FOR NEXT INSPECTION 6. RECALL WHEN READY |