Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ACCESS 1:43 PM |
|
| 09/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED A 2 GROUND RODS 6' APART AND CONTINOUS INTO SERVICE PANEL 2) NEED TO PLUG HOLE IN BOTTOM OF SERVICE PANEL 3) WILL NEED TO INDENTIFY ALL BREAKERS BEFORE FINALS 4) NEED TO POST ADDRESS ON SERVICE 5) WILL NEED TO BOND WATER AND GAS 6) WATER HEATER NEEDS TPR VALVE-3/4 TERMINATED TO OUTSIDE BLDG 7) NEED VALVE ON COLD WATER SIDE 8) GAS LINE AT WATER HEATER NEEDS SEDIMENT TRAP |
|
| 09/03/2008 | ELECTRIC - FINAL | Cancelled | CANCELLED PER HOMEOWNER ALEXIS AGUILAR #304-1970 | |
| 09/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED ACCESS TO INTERIOR TO DO RECONNECT INSPECTION |