Permit: T08EL01620

Parcel: 116310010

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T08EL01620

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
08/27/2008 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
08/26/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. MAINTAIN CLEARANCE IN FRONT OF BREAKER PANEL - 110.26 NEC
2. CODE REQUIRES 36" IN FRONT BY 30" HORIZONTAL DEDICATED SPACE (UNOBSTRUCTED)
3. STACKED, WASHER/DRYER UNIT IN SPACE