Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXISTING GROUNDING ELECTRODE CONDUCTOR WAS CUT, MUST BE RESTORED PRIOR TO POWER RELEASE! |
|
| 09/12/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 2 GROUND RODS REQUIRED 6' MIN. APART 2. NEUTRAL TO BE BANDED IN SERVICE DISCONNECT DISCONNECT 3. GROUNDING ELECTRODE SYSTEM MUST BE COMMON |
|
| 08/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TENANT TO HAVE ACCESS TO SERVICE 2. DISCONNECT SW WILL NOT SHUT OFF 3. GROUNDING ELECTRODE SYSTEM HAS BEEN CUT OFF |