Permit: T08EL01538

Parcel: 140291700

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/28/2008 ELECTRIC - FINAL Approved IVRS - Inspection :$
08/27/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE ALL EXPOSED ROMEX AND BOXES FROM BBQ AREA
08/21/2008 ELECTRIC - FINAL Denied ROMEX FROM LIGHT FIXTURE AT PORCH TO FIXTURE AT FACIA NOT WIRED CORRECTLY FIXTURE USED AS A J-BOX, FIXTURE AT PORCH NOT LISTED FOR EXTERIOR USE TOO CLOSE TO END IF OVER HANG, FROM LAST INSPECTION PLUG HOLE IN SERVICE PANEL. REMOVE CU. PIPE AND ALL EXPOSED ROMEX
08/14/2008 ELECTRIC - FINAL Denied