Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/26/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SMOKE DETECTORS TO BE MIN. 3' FROM AIR SUPPLY DUCTS AND HIGH AIR FLOW AREAS. SEE INSTRUCTIONS. |
|
| 08/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REPLACE BROKEN PLATE @ RANGE RECEPTACLE 2. ALL KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED 3. MISSING FAN OVER RANGE WIRES JUST HANGING OUT OF WALL 4. INSTALL SMOKE DETECTORS IN ALL BEDROOMS AND ONE OUTSIDE OF BEDROOMS PER INSTRUCTIONS 5. EXPOSED WIRES IN PANTRY CLOSET 6. INSTALL DRYER RECEPTACLE PLATE |