Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/20/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO POWER TO RECEPTACLES ON SOUTHWALL OF LIVING ROOM 2) GFI RECEPTACLE AT BATHROOM NOT RESETTING |
|
| 08/12/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ALL 3 PRONG OUTLETS, THAT ARE ON THE 2 WIRE SYSTEM, MUST BE CHANGED BACK TO 2 PRONG OUTLETS OR MADE GFI PROTECTED AS UN-GROUNDED OUTLETS 2) LABEL ALL BREAKERS AFTER RECONNECT, FOR FINAL INSPECTION |