Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/11/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO GROUND SERVICE AND BOND GAS LINE. WILL NEED 2 GROUND RODS 6' APART 2) RECEPTACLES AT KITCHEN COUNTER MUST BE GFI PROTECTED 3) ALL SWITCHES AND RECEPTACLES MUST HAVE COVER PLATES 4) NEED SMOKIES IN BEDROOMS AND HALLWAY 5) NEED TO REPAIR ELECTRICAL WIRING IN JACK-N-JILL BATHROOM RECEPTACLE IN BATH MUST BE GFI PROTECTED 6) NEED TO REMOVE WASP HIVE FROM FRONT PORCH TO INSPECT LOOSE WIRE 7) WAS ADDED BEDROOM WITH BATH PERMITTED ? NEED TO SHOW PROOF |