Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T08EL01477
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/18/2008 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* 1) OK CORRECTIONS 2) OK TO CLEAR |
|
08/14/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEED TO REPLACE/REPAIR GROUNDING ELECTRODE SYSTEM TO ALL THREE SERVICES ON BUILDING. ENSURE WATER PIPING SYSTEM BONDED ALSO, PER NEC 250 |
|
08/12/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE PREVIOUS INSPECTION SITES INSTALL NEW GROUNDING ELECTRODE SYSTEM OR REPAIR EXISTING PER NEC 250 ON ALL THREE SERVICES |
|
08/07/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |