Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2008 | FIRE - FINAL | Approved | Approved 8/26/08. | |
| 08/22/2008 | FIRE - FINAL | Denied | Door locked. 8/21/08. | |
| 08/08/2008 | FIRE - FINAL | Denied | Not approved 8/8/08. 1.) Signage over main exit door reading: " THIS DOOR TO REMAIN UNLOCKED WHEN BUIKLDING IS OCCUPIED" 2.) Remove slide-bolt locks from all exterior doors. 3.) Provide thumb-turn locks for NE & NW exterior . 4.) Provide thumb-turn lock on the egress side of door inside othe workshop area. 5.) Provide thumb-turn lock on the egress side of door the Crib area. 6.) Cover plates a.) main floor, ceiling, next to rool-up door. b.) office area, second floor. 7.) lable door to electrical panal " ELECTRICAL" 8.) Exit sign over main exit door is burnt out. 9.) Provide lighted exit sign directing pass to main exit. |
|