Permit: T08EL01454

Parcel: 130170360


Addresses:

3948 E 27TH ST


Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL01454

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
08/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPLACE PVC LINE IN BATHROOM WITH COPPER OR GALV. IRON PIPE AND IN WATER HEATER ROOM
2) CHECK OFFICE FILES, CONFIRM THAT CARPORT ENCLOSURE, STORAGE ADJACENT TO BEDROOM AND REAR METAL ROOF STRUCTURE ARE PERMITTED, IF NOT OBTAIN PERMITS
3) PROVIDE OPERABLE/WORKING SMOKE ALARMS IN BEDROOMS AND HALLWAY
4) PROTECT ALL ELECTRIC WIRE WITHIN 8' OF FLOOR