Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) WILL TEST GFI CIRCUITS AT KITCHEN WHEN POWER IS ON 2) NEED TO IDENTIFY ALL BREAKERS AT SUB PANEL |
|
| 07/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN AND BATH RECEPTACLES MUST BE GFI PROTECTED 2) MISSING SMOKE DETECTORS AT BEDROOM AND HALLWAY 3) MAIN FEEDER MUST BE LISTED FOR EXT APPLICATION OR YOU NEED TO PUT IN CONDUIT GOING TO SERVICE PANEL 4) ALL CONDUCTOR WIRES IN RISER FROM SERVICE PANEL NEED TO BE IN A JUNCTION BOX 5) NEED TO BLANK ALL OPENINGS IN DEAD FACE COVER 6) NEED TO POST ADDRESS ON SERVICE PANEL AND AT METER-NEED MORE CLARITY 7) WILL NEED TO IDENTIFY ALL BREAKERS 8) NEED TO GROUND SERVICE PANEL (2-GROUND RODS 6' APART) 9) NEED TO BOND GAS AND WATER LINES |