Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL01396
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/26/2008 | ELECTRIC - FINAL | Approved | ||
08/19/2008 | ELECTRIC - FINAL | Cancelled | CANCELLED PER FRED BURGE #269-6199 | |
08/19/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO HAVE APPROVED PERMIT AND LAYOUT OF NEW ADDITION DINING ROOM AND BEDROOM SHOWING ELECTRICAL AND MECHANICAL |
|
07/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO SHOW PERMITTED WORK FOR ENCLOSURE OF CARPORT ? (LOOKS LIKE WORK DONE WITHOUT PERMITS) 2) RECEPTACLE BOX NEEDS TO BE COMPLETED AT ENTRY TO ADDITION 2 PLACES 3) RECEPTACLE ON NORTH WALL OF LAUNDRY ROOM NEEDS TO BE INSTALLED CORRECTLY (ENCLOSED CARPORT) 4) MISSING SMOKIES IN BEDROOMS 5) NEED KNOCKOUT PLUG AT MAIN BREAKER PANEL (IN BOTTOM) 6) ALUMINUM WIRES NEED NO-LOX 7) NEED SHOW GROUNDING OF SERVICE PANEL, ALL I SEE IS MAYBE A BONDING OF GAS OR WATER |