Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2010 | ELECTRIC - FINAL | Approved | ||
| 08/18/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO SECURE RISER TO BLDG 2) NEED TO POST ADDRESS ON SERVICE PANEL 3) NEED TO GROUND SERVICE (ALL I SEE IS A WATER BOND) 2 GROUND RODS 6' APART INTO GROUND WITH #8 WIRE 4) ALL RECEPTACLES MUST HAVE FACE PLATES 5) KITCHEN RECEPTACLES MUST BE GFI PROTECTED 6) ALL LIGHT FIXTURES MUST BE COMPLETED OR BLANKED 7) NEED TO SHOW PROOF OF PERMITS FOR ROOM ADDED AT REAR OF HOUSE (CODE VIOLATIONS) 8) NEED SMOKIES IN BEDROOM AND HALLWAY |