Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/24/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROTECT CORD FROM CASES 2. RECEPTACLE IN WALL COMING OUT 3. TIGHTEN LINE CONDUCTORS AT SUB-PANEL 4. SEPARATE GROUNDS AND NEUTRALS AT SUB-PANEL 5. SERVICE GROUNDING ELECTRODE MISSING 6. USE APPROVED CORD FOR SHOW CASES - NOT CUT EXTENSION CORD 7. EXPOSED CONDUCTOR ABOVE CEILING |