Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/01/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) WILL REINSPECT AFTER POWER IS ON |
|
| 07/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) YOU MUST EXPOSE YOUR GROUND ROD SYSTEM FOR INSPECTION MUST BE ABLE TO VERIFY 2) 2 GROUND RODS MINIMUM 6' APART MUST BE ABLE TO VERIFY WATER AND GAS BONDS |
|
| 07/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEM FROM PRIOR INSPECTION ON 7/25/08 HAVE NOT BEEN MET 2) CALLED NUMBER LISTED AND NO ANSWER |
|
| 07/25/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXPOSE BOTH GROUND RODS 2) EXPOSE #4 BOND TO WATER AND GAS |
|
| 07/16/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED GRD. RODS, H20 BOND, GAS BOND, HAVE BEEN CUT 2) EXPOSED ROMEX AT KITCHEN COUNTER AND CLOSET UNDER STAIR 3) MAKE SURE BEDROOM WINDOW BARS OPEN WITHOUT TOOLS OR SPECIAL KNOWLEDGE 4) NEED HOUSE ADDRESS ON BLDG |