Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GFCI RECEPTS NORTH SIDE OF SINK WON'T TRIP WHEN TESTED WITH A GFCI TRIP TESTER. CHECK LINE LOAD FOR PROPER MANUFACTURER CONNECTION NOT JUST HOT/NEUTRAL 2) YOU HAVE TWO COUNTER TOP CIRCUITS SHOULD ONLY REQUIRE TWO GFCI'S |
|
| 07/16/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CALL BACK FOR FINAL 2) FIX SMOKE DETECTORS 3) SHOULD BE 2 GFCI RECEPTS AT KIT COUNTER |