Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* EQUIP. BONDING ON SUPPLY SIDE OF SERVICE MUST BE PER 250.102 CONDUCTOR SIZE PER 250.66 |
|
| 08/26/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. TIGHTEN LOOSE FITTINGS 2. NEED REJECTION PINS 3. VERIFY FAULT CURRENT FOR SERVICE 4. VERIFY EXISTING CONDUITS AND CONDUCTORS 5. FINISH PANEL MAKE UP 6. SUPPORT RISER 7. CABLE BRACING REQUIRED |