Permit: T08EL01293

Parcel: 10713106A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/08/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
EQUIP. BONDING ON SUPPLY SIDE OF SERVICE MUST BE
PER 250.102 CONDUCTOR SIZE PER 250.66
08/26/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. TIGHTEN LOOSE FITTINGS
2. NEED REJECTION PINS
3. VERIFY FAULT CURRENT FOR SERVICE
4. VERIFY EXISTING CONDUITS AND CONDUCTORS
5. FINISH PANEL MAKE UP
6. SUPPORT RISER
7. CABLE BRACING REQUIRED