Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL01258
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/16/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING ELECTRODE CONDUCTOR CUT & STOLEN INSTALL NEW GROUNDING ELECTRODE SYSTEM BOND GAS & WATER PIPING 2. INSTALL FUSES AND TERMINATE WIRES IN SERVICE DISCONNECT 3. INSTALL MAIN BONDING JUMPER IN SERVICE DISCONNECT 4. REPLACE ALL PAINTED OVER RECEPTACLES 5. INSTALL GE BREAKERS IN GE PANEL |