Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NO WORK PROGRESS |
|
| 09/17/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK MAIN 1. NO LOADS CONNECTED AT THIS TIME - PLANS CALL FOR LIGHTS 2. PANEL BREAKER LABELING TO BE AS PER 408.4 - NO ABBREVIATION |
|
| 09/15/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* MAIN BREAKER TO BE RATED AT 22KAIC PER APPROVED PAPERWORK |
|
| 09/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MAIN BRK NOT RATED FOR AVAIL. FAULT CURRENT 31K 2. PROVIDE C.O.T APPROVED PLAN |