Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/10/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 07/02/2008 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* CALL AFTER CHANGE OVER |
|
| 06/27/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT - NEC 250.6 2. BOND GROUNDED CONDUCTOR TO SERVICE DISCONNECT ENCLOSURE - NEC 250.24C 3. GROUNDING ELECTRODE CONDUCTOR TO CONNECT TO GROUNDED CONDUCTOR - READ NEC 250.24A, A4 4. BOND ALL PIPING AND STEEL TO SERVICE AS REQUIRED BY NEC 250.104 - PROVIDE INTERIOR ACCESS SO I CAN VERIFY 5. RUN GROUNDING ELECTRODE CONDUCTOR UP WALL IN PVC TO PROTECT IT FROM BEING STOLEN. |