Permit: T08EL01139

Parcel: 121113250


Addresses:

4805 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL01139

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/18/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/17/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTE #1 LAST INSP.
07/15/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HUBS MUST BE LISTED FOR BONDING AT SERVICES 250.94
2. ARRANGE CONDUCTORS SO AS TO NOT CREATE A PARALLEL PATH ON GROUNDING & GROUNDED CONDUCTORS
3. LABEL EQUIP. AT SERVICE
07/08/2008 ELECTRIC - FINAL Cancelled IVRS - RI canceled