Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL01122
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/24/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* UNIT LOCKED. NO ACCESS |
|
| 06/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BATHROOM RECEPTACLES TO BE GFI PROTECTED 2. GROUNDING ELECTRODE CONDUCTOR CUT & STOLEN INSTALL NEW GROUNDING ELECTRODE SYSTEM FOR SERVICE 3. INSTALL MAIN BONDING JUMPER IN SERVICE DISCONNECT 4. TERMINATE NEUTRALS TO NEUTRAL BAR IN PANEL 5. INSTALL ALL DEVICE PLATES 6. RECALL WHEN READY 7. PROVIDE LADDER FOR ROOF ACCESS |