Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/05/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 4/0 AL CONDUCTORS REQUIRED FOR 200 AMP SERVICE 3/0 INSTALLED 2) IF THERE IS NATURAL GAS, AT THIS HOUSE GAS BOND REQUIRED |