Permit: T08EL01072

Parcel: 115040790

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL01072

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
06/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SMOKE DETECTORS NOT MOUNTED IN LOCATIONS REQUIRED IN INSTRUCTIONS, ALSO TO BE MINIMUM 36" FROM HVAC VENTS. READ INSTALL INSTRUCTIONS
06/13/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED ADDRESS POSTED ON BUILDING
2. SERVICE DISCONNECT TO BE IDENTIFIED "UNIT C"
3. SERVICE DISCONNECT MISSING PROPER HUB FOR
METER NIPPLE
4. SERVICE DISCONNECT MISSING NEUTRAL BOND SCREW
5. NEED GFI PROTECTION FOR ALL KITCHEN COUNTER AND BATHROOM LIGHT RECEPTACLES
6. NEED NEW SMOKE DETECTORS EACH BEDROOM AND HALLWAY - INSTALL PER MANUFACTURES INSTRUCTIONS