Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/07/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED REVISION FOR PANEL SCHEDULES. SEE NOTE ON PERMIT 2. NEED OVERCURRENT PROTECTION FOR XFMR SECONDARIES 3. PLAN CALLS FOR 90 AMP BREAKER TO FEED XFMR 4. WIRING XFMR OK |