Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2008 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 06/09/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GAS PIPING TO BE BONDED ON BUILDING SIDE OF METERS 2. GROUNDING ELECTRODE CONDUCTOR SPLICE TO BE BY EXOTHERMIC WELD OR IRREVERSIBLE CRIMP CANNOT USE SPLIT BOLT. |
|
| 06/05/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : There is no access to the site.| 920* UNIT LOCKED. NO ACCESS. ENSURE ALL PREVIOUS INSPECTION ITEMS CORRECTED BEFORE RESCHEDULING INSPECTION |
|
| 06/04/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE RECEPTACLE HANGING OUT OF CEILING IN FRONT OF STORE 2. SECURE INDUSTRIAL COVERS TO BOXES 3. UNLOCK FUSE PANEL. INSTALL PROPER FUSES SIZES FOR CIRCUITS 4. SEAL OPEN BREAKER POSITIONS IN PANEL 5. ONE NEUTRAL PER TERMINAL IN PANEL 6. NEUTRALS & GROUNDS TO BE SEPARATE IN PANELS INSTALL GROUND BAR TO TERMINATE GROUNDS 7. REMOVE EXTENSION FROM LIGHT IN RESTROOM 8. WIRING IN BOILER ROOM NOT CODE COMPLIANT NEEDS TO BE ADDRESSED 9. GROUNDING ELECTRODE CONDUCTOR CUT AND REMOVED FROM SERVICE. INSTALL NEW GROUNDING ELECTRODE SYSTEM AND BOND GAS AND WATER PIPING 10. NEED PANEL DIRECTORIES 11. HAVE QUALIFIED ELECTRICIAN MAKE CORRECTIONS 12. HAVE OPEN WIRING. TO BE REMOVED. |