Permit: T08EL00994

Parcel: 131090030


Addresses:

5858 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
06/11/2008 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
06/09/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GAS PIPING TO BE BONDED ON BUILDING SIDE OF METERS
2. GROUNDING ELECTRODE CONDUCTOR SPLICE TO BE BY EXOTHERMIC WELD OR IRREVERSIBLE CRIMP CANNOT USE SPLIT BOLT.
06/05/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
There is no access to the site.| 920*
UNIT LOCKED.
NO ACCESS.
ENSURE ALL PREVIOUS INSPECTION ITEMS CORRECTED BEFORE RESCHEDULING INSPECTION
06/04/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE RECEPTACLE HANGING OUT OF CEILING IN FRONT
OF STORE
2. SECURE INDUSTRIAL COVERS TO BOXES
3. UNLOCK FUSE PANEL. INSTALL PROPER FUSES SIZES FOR CIRCUITS
4. SEAL OPEN BREAKER POSITIONS IN PANEL
5. ONE NEUTRAL PER TERMINAL IN PANEL
6. NEUTRALS & GROUNDS TO BE SEPARATE IN PANELS
INSTALL GROUND BAR TO TERMINATE GROUNDS
7. REMOVE EXTENSION FROM LIGHT IN RESTROOM
8. WIRING IN BOILER ROOM NOT CODE COMPLIANT
NEEDS TO BE ADDRESSED
9. GROUNDING ELECTRODE CONDUCTOR CUT AND REMOVED FROM SERVICE. INSTALL NEW GROUNDING ELECTRODE SYSTEM AND BOND GAS AND WATER PIPING
10. NEED PANEL DIRECTORIES
11. HAVE QUALIFIED ELECTRICIAN MAKE CORRECTIONS
12. HAVE OPEN WIRING. TO BE REMOVED.