Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2008 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 09/10/2008 | ELECTRIC - RECONNECT | Partial Approval | IVRS - Inspection :* 1) ITEM #17 HAS BEEN MET, WILL REINSPECT AT FINALS INSPECTOR WAS INCORRECT PER CARLOS, SHOULD HAVE BEEN MET AND HAS NOT |
|
| 08/13/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOTE: 13, 16 & 17 FROM PREVIOUS |
|
| 06/03/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL UNIT NUMBER 2) REPLACE FRONT LIGHT FIXTURE 3) PROVIDE WEATHERED CONNECTORS ALL EXTERIOR ROMEX. PROTECT FROM PHYSICAL DAMAGE ALL EXTERIOR BOXES 4) LABEL CIRCUITS SUB PANEL 5) HAZARDOUS ELECTRICAL COOLER CONNECTION 6) GFCI PROTECT EXTERIOR OUTLETS 7) PROVIDE EXTERIOR LIGHT FIXTURE KITCHEN EXTEND DOOR 8) GFCI PROTECT KITCHEN OUTLETS 9) HAZARDOUS ELECTRICAL KITCHEN LIGHT FIXTURE 10) MISSING COVER PLATES THROUGHOUT 11) HAZARDOUS ELECTRICAL LIVING ROOM CEILING FIXTURE 12) PROVIDE WORKING SMOKE DETECTORS 13) PROVIDE SAFE EGRESS TO EXTERIOR BEDROOM WINDOW 14) MISSING GLOBE BATH FIXTURE 15) PROTECT CLOSET ROMEX FROM PHYSICAL PROTECTION 16) GROUND MAIN SECURE PANEL GROUND ROD SYSTEM 17) PROVIDE GAS AND WATER BOND |