Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/13/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* DOOR IS LOCKED/NO ANSWER |
|
| 06/02/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED ACCESS TO SERVICE & IDENTIFY SERVICE DISCONNECT 2. PROVIDE GFI PROTECTION FOR KITCHEN COUNTER RECEPTACLES 3. MOUNT NEW SMOKE DETECTOR TO LIVING ROOM CEILING 4. REPLACE PAINTED OVER DEVICES 5. GROUNDING TYPE RECEPTACLE NOT ALLOWED ON CKT 6. INSTALL MISSING GLOBE KITCHEN LIGHT 7. MAX. 60 WATT BULBS IN LIGHT FIXTURES |